Engineering note: This tool performs preliminary PSV orifice sizing per the standard API RP 520 metric equations. Final valve selection, Kb/Kw/Kv correction factors, rated capacity certification, inlet/outlet piping (3% / 10% pressure-drop checks per API 520 Part II), and relief-header backpressure analysis must be verified by the responsible process/safety engineer and cross-checked against vendor capacity certification (NB/ASME) data before issue for construction / MOC closure.
1. General / Common Data
10% single valve; 16% fire case; 21% supplemental
✕Kd — Effective Coefficient of Discharge (vapor/steam). Standard value 0.975 for a certified PRV. Not read from a curve — it is the ASME/NB-certified value stamped on the valve nameplate.
Ref: API RP 520 Part I, §5.6.
Ref: API RP 520 Part I, §5.6.
✕Kd — Effective Coefficient of Discharge (liquid). Standard value 0.65 for a certified PRV in liquid service; 0.62 when sizing a rupture disc alone (no PRV).
Ref: API RP 520 Part I, §5.6.
Ref: API RP 520 Part I, §5.6.
1.0 conventional; from Fig.30/31 for bellows
✕Kb — Capacity Correction Factor for Backpressure, vapor/gas. Kb = 1.0 for conventional (non-bellows) valves within the allowable backpressure limit. For balanced-bellows valves, read from the backpressure-ratio curve.
Ref (7th Ed.): Fig.30 (bellows, vapor/gas); Fig.35 (conventional, when backpressure exceeds normal limit). Figure numbers shift between editions — confirm against your copy of API RP 520 Part I.
Ref (7th Ed.): Fig.30 (bellows, vapor/gas); Fig.35 (conventional, when backpressure exceeds normal limit). Figure numbers shift between editions — confirm against your copy of API RP 520 Part I.
✕Kw — Capacity Correction Factor for Backpressure, liquid, balanced-bellows valves. Kw = 1.0 for conventional valves; for bellows valves, read from the backpressure-ratio curve.
Ref (7th Ed.): Fig.31. Numbering varies by edition — confirm against your copy.
Ref (7th Ed.): Fig.31. Numbering varies by edition — confirm against your copy.
1.0 = no RD upstream; 0.9 = with RD
✕Kc — Combination Correction Factor, rupture disc upstream of PRV. Kc = 1.0 with no rupture disc; 0.9 when a disc + PRV combination has not been NB-certified together (use the certified Combination Capacity Factor if available). Formula/table-based, not read from a figure.
Ref: API RP 520 Part I, §5.6.5 / §5.7.
Ref: API RP 520 Part I, §5.6.5 / §5.7.
1.0 if Re>~100,000 (light HC); else from API 520 curve
✕Kv — Viscosity Correction Factor, liquid service. Function of Reynolds number at the trial orifice area (iterative). Kv = 1.0 for turbulent flow (Re typically > ~16,000–100,000, most light hydrocarbons).
Ref: API RP 520 Part I, viscosity-correction curve (numbered Fig.33/34 depending on edition — confirm against your copy).
Ref: API RP 520 Part I, viscosity-correction curve (numbered Fig.33/34 depending on edition — confirm against your copy).
2. Equipment Fire-Exposed Area Module (API RP 521 §4.4 / Annex D)
Add every item of equipment within the common fire-exposed zone (vessel, drum, exchanger shell, compressor casing, etc.) protected by this PSV / relief header. Each item computes its own wetted (liquid-containing) or total exposed (gas-filled) surface area from its geometry, or a direct area entry — the areas are then summed to a single Total Fire-Exposed Area which feeds the Fire Case tab. One common Environmental Factor F and drainage credit is applied to the summed area (standard API 521 practice for a shared fire zone).
Total Fire-Exposed Area (sum of all equipment), A
— m²
— m²
3. Relief Load Cases
Step 1 — Select PSV Duty / Fluid State
Gas/Vapor PSV selected — applicable relief scenarios shown below: External Fire, Blocked Outlet/CV Fail, Tube Rupture. Switch above to change fluid state; the summary in Section 4 will only compare cases relevant to the selected duty.
Step 2 — Applicable Relief Scenarios
Case 1: External Fire
Case 2: Blocked Outlet / CV Fail
Case 3: Liquid Thermal Expansion
Case 4: Exchanger Tube Rupture
Case 5: Blocked Outlet (Liquid)
Case 1 — External Pool Fire (API RP 521 §4.4)
Heat Input, Q
— kW
— kW
Vapor Relief Load, W
— kg/hr
— kg/hr
Required Orifice Area
— mm²
— mm²
Case 2 — Blocked Discharge / Control Valve Fail-Open / Gas Blowby (Vapor)
Required Orifice Area
— mm²
— mm²
Case 3 — Liquid Thermal Expansion (blocked-in liquid-full line/exchanger, API 521 §4.14)
Q_relief (m³/hr) = (β × H × 3600) / (ρ × Cp) — β = cubical expansion coeff. (1/°C), H = heat input (kW), ρ = density (kg/m³), Cp = specific heat (kJ/kg·°C). This case typically governs the smallest orifice (often D or E) and is rarely limiting.
Cubical Expansion Coefficient, β — Guideline (API RP 521, Table 2)
heavier liquid (higher SG) → lower β; lighter liquid → higher β
Heat Input, H — Guideline & Helper
Two recognized bases are commonly used for the blocked-in thermal relief heat input, per API RP 521 and widely-published industry practice (not a single fixed API equation — engineering judgment applies):
- Solar radiation on the exposed surface of the blocked-in, liquid-full line/equipment: typical design flux 0.79–1.04 kW/m² (≈250–330 Btu/hr·ft²), applied to the exposed (or projected) surface area. Use the lower end for temperate climates / part-insulated lines, the upper end for full tropical sun exposure on bare pipe.
- Heat exchanger duty, when the blocked-in liquid is on one side of an exchanger and the other side continues to circulate a hot medium — use the actual exchanger duty from the datasheet/simulation (this is normally far larger than the solar case and will govern if applicable).
solar / fire exposure / adjacent hot stream
Volumetric Relief Rate, Q
— m³/hr
— m³/hr
Required Orifice Area
— mm²
— mm²
Case 4 — Heat Exchanger Tube Rupture (API 521 §4.9, single-tube rupture rule)
Flow through a single ruptured tube is taken as twice the flow area of one tube (conservative rule-of-thumb, full-bore rupture), based on the high-pressure side conditions flashing/flowing into the low-pressure side. Flow computed via nozzle equation at tube-rupture ΔP.
Tube-Rupture Relief Load, W
— kg/hr
— kg/hr
Required Orifice Area
— mm²
— mm²
Case 5 — Blocked Outlet / Pump Deadhead / Overfilling (Liquid)
Required Orifice Area
— mm²
— mm²
4. Governing Case Summary & PSV Selection
| Relief Case | Basis | Relief Load | Required Area, mm² | Selected Std. Orifice | Orifice Area, mm² |
|---|---|---|---|---|---|
| Click "Calculate All Cases" to populate summary | |||||
Governing Case (Maximum Required Area)
—
—
API Standard Orifice Reference — API 526 (Horizontal Table)
Multiple flange-rating combinations exist per API 526 for a given orifice letter (e.g., 3J4, 3"×4" 150#/300#/600# etc.). The table above lists the most commonly applied inlet×outlet flange size; confirm final selection with valve vendor GA drawing, inlet piping 3% pressure-drop check and outlet piping built-up backpressure check (API 520 Part II) before MOC/PO issue.